Cooling method of dry transformer
Dry transformer cooling methods are divided into natural air cooling (AN) and forced air cooling (AF). When air cooled naturally, the transformer can run continuously for a long time under the rated capacity. When forced air cooling, the transformer output capacity can be increased by 50%. Suitable for intermittent overload operation, or emergency overload operation; Due to the large increase in load loss and impedance voltage during overload, it is in a non-economic operation state, so it should not be kept in continuous overload operation for a long time.
Type |
Voltage Combination |
Connection Symbol |
No-Load Loss (kW) |
120ºC (kW) |
No-Load Current (%) |
Impedance Voltage (%) |
Sound Level dB |
Weiht (kg) |
Exient of the Base Framework |
Overall Dimension ×× Length×Width×High |
OverallDinension ×× Length×Width×High |
||
H.V (kV) |
Tapping Range of H.V (%) |
L.V (kV) |
|||||||||||
SC11-30 | 6 6.3 6.6 10 10.5 11 |
±5 ±2×2.5 |
0.4 | Yyn0 Dyn11 |
0.168 | 0.705 | 3.2 | 4.0 | 45 | 662 | 550×700 | 940×655×955 | 1800×1258×1768 |
SC11-50 | 0.238 | 0.994 | 2.8 | 45 | 717 | 940×655×1005 | |||||||
SC11-80 | 0.322 | 1.377 | 2.6 | 46 | 772 | 1000×705×1055 | |||||||
SC11-100 | 0.350 | 1.572 | 2.4 | 46 | 937 | 1100×705×1155 | |||||||
SC11-125 | 0.413 | 1.844 | 2.2 | 49 | 992 | 1100×705×1205 | |||||||
SC11-160 | 0.476 | 2.125 | 2.2 | 49 | 1158 | 550×810 | 1120×705×1166 | ||||||
SC11-200 | 0.546 | 2.524 | 2.0 | 49 | 1158 | 1120×705×1281 | |||||||
SC11-250 | 0.630 | 2.754 | 2.0 | 49 | 1257 | 660×1000 | 1230×818×1264 | ||||||
SCB11-315 | 0.770 | 3.468 | 1.8 | 51 | 1511 | 1230×818×1382 | |||||||
SCB11-400 | 0.854 | 3.986 | 1.8 | 51 | 1698 | 1230×818×1498 | |||||||
SCB11-500 | 1.015 | 4.879 | 1.8 | 52 | 1986 | 1280×818×1587 | |||||||
SCB11-630 | 1.176 | 5.873 | 1.6 | 52 | 2582 | 820×1000 | 1600×1010×1530 | 2030×1360×1850 | |||||
SCB11-800 | 1.330 | 6.953 | 1.6 | 6.0 | 54 | 3016 | 1675×1010×1640 | ||||||
SCB11-1000 | 1.547 | 8.126 | 1.4 | 54 | 3562 | 1750×1010×1736 | 2130×1460×2060 | ||||||
SCB11-1250 | 1.827 | 9.690 | 1.4 | 55 | 4174 | 1780×1010×1846 | |||||||
SCB11-1600 | 2.142 | 11.73 | 1.4 | 56 | 5899 | 1825×1015×1901 | 2400×1615×2165 | ||||||
SCB11-2000 | 2.905 | 14.45 | 1.2 | 56 | 6678 | 2020×1015×1981 | |||||||
SCB11-2500 | 3.500 | 17.17 | 1.2 | 60 | 7902 | 2030×1015×1968 | 2400×1615×2265 |